Cooling Tower Not Cooling? 7 Warning Signs to Check Before You Call

The seven warning signs a commercial HVAC technician checks first when a cooling tower isn’t cooling — from scale buildup to a rising approach temperature — and how to tell an early problem from an emergency.

By B&B Mechanical Team Published Updated

If your cooling tower is running but your building still isn’t cooling properly, the seven warning signs below — from scale buildup on the fill media to a rising approach temperature — are what a commercial HVAC technician checks first. Catching them early keeps a tower running efficiently and helps avoid an emergency shutdown during peak cooling season across San Diego County.

Why Cooling Towers Fail Quietly

A cooling tower rarely fails all at once. Because it rejects heat by evaporating a small percentage of the water passing through it, a tower can keep running for weeks or months with degraded performance before anyone notices the building is running warmer than it should. By the time occupants complain, the underlying issue has usually been building for a while — which is exactly why a short, regular visual and mechanical check catches problems while they’re still cheap to fix.

7 Warning Signs to Check

1. Scale and Mineral Buildup on the Fill Media

Fill media is where the actual heat exchange happens — water is spread thin across it so air can evaporate a portion as it passes through. Hard-water minerals (common throughout San Diego County’s water supply) deposit on that surface over time, insulating it from the airstream and quietly reducing cooling capacity long before the tower looks visibly dirty.

2. Reduced or Uneven Water Distribution

Clogged spray nozzles or a cracked distribution basin cause water to pool in some areas of the fill and starve others. The result is a tower that “sounds” normal but isn’t using its full fill surface area, which shows up as reduced cooling capacity under peak load.

3. Fan Belt Slipping or Motor Bearing Noise

A squealing belt or a grinding/humming bearing is one of the few warning signs you can catch by ear during a routine walk-through. Left alone, a slipping belt reduces airflow across the fill (and therefore cooling capacity), and a failing bearing can seize the fan motor entirely.

4. Rising Approach Temperature

Approach temperature — the difference between the water leaving the tower and the outdoor wet-bulb temperature — is the single best number for tracking tower health over time. A tower in good condition holds a fairly consistent approach; a steadily rising approach reading across successive service visits is the clearest sign something in the heat-transfer path is degrading.

5. Algae or Biological Growth in the Basin

Warm, standing water in a basin is a natural environment for biological growth if water treatment lapses. Beyond the performance impact (biofilm fouls fill media the same way scale does), untreated basin water is one of the conditions associated with Legionella risk, which makes this a compliance and safety issue as much as a mechanical one.

6. Visible Water Carryover Past the Drift Eliminators

Drift eliminators are designed to strip water droplets out of the exhaust air stream before it leaves the tower. Visible mist or water spray drifting away from the tower usually means the eliminators are damaged, missing, or improperly seated — a straightforward repair if caught early, but a source of real water loss and nearby surface staining if ignored.

7. Corrosion on the Structure, Basin, or Fan Shroud

Coastal marine-layer exposure — a real factor for towers in La Jolla, Point Loma, Coronado, and Del Mar — accelerates corrosion compared to inland installations. Surface rust on structural steel or a corroding basin isn’t just cosmetic; it’s the warning sign that most often turns into a structural, rather than mechanical, decision.

When a Warning Sign Means Repair vs. Replacement

Some of these signs point to a straightforward repair; others are early indicators that a tower is nearing the end of its useful service life. Cooling Tower Repair vs. Replacement: A Cost & Decision Framework walks through how to tell the difference before you commit to either path.

Related reading: Condenser Water Pump Maintenance Checklist for Facility Managers and Boiler Short-Cycling and Other Warning Signs Facility Teams Miss.

B&B Mechanical services commercial cooling towers across San Diego County, and our project portfolio includes multiple cooling tower retrofits for facilities that caught these signs early enough to plan the work rather than react to a failure.

Frequently Asked Questions

How often should a commercial cooling tower be inspected?

Most manufacturer guidance calls for a full mechanical and water-quality inspection at least quarterly, with a visual check of the basin, fill, and drift eliminators monthly during the cooling season.

Can scale buildup really reduce cooling capacity?

Yes. Scale on fill media insulates the water film from the airstream, which is the primary heat-transfer mechanism in an evaporative cooling tower — even a thin layer measurably raises the tower’s approach temperature.

Is algae growth in a cooling tower basin a safety issue, not just a performance one?

It can be. Untreated basin water is one of the conditions associated with Legionella growth, which is why water treatment and basin cleaning schedules matter for compliance and occupant safety as much as for cooling performance.

What causes a rising approach temperature over time?

Approach temperature rises when heat-transfer surfaces — fill media, spray nozzles — are fouled, when airflow is restricted by a fan or belt issue, or when water distribution across the fill has become uneven.

Do I need to shut the whole system down to inspect the tower?

A basin and fill visual inspection can typically be done without a full shutdown. Belt, bearing, and fan inspections generally require the tower to be de-energized for technician safety.

Related Glossary Terms

Terms used in this guide

Approach Temperature
Approach temperature is the difference between the water leaving a cooling tower and the outdoor wet-bulb temperature, and it's the single best number for tracking a tower's health over time. A tower in good condition holds a fairly consistent approach; a steadily rising approach signals degrading heat transfer.
Cooling Tower Range
Range is the temperature drop across a cooling tower: hot condenser water in minus cooled water out. Range is set by the heat the chiller rejects and the water flow; a collapsing range usually points to a flow problem, not the tower itself.
Wet-Bulb Temperature
Wet-bulb temperature is the lowest temperature air can reach through evaporation at its current humidity. It sets the floor for how cold a cooling tower can make its water, which is why towers are rated against design wet-bulb, not dry-bulb, conditions.
Makeup Water
Makeup water replaces what a cooling tower loses to evaporation, drift and blowdown, and what a closed hydronic loop loses to leaks. A rising makeup meter on a closed loop is a leak indicator; on a tower it tracks load and water quality.
Have a question?

Talk to a real technician.

Tell us what's going on and our San Diego team will reach out. For emergencies, call us 24/7 at (619) 713-0400.

Call us 24/7(619) 713-0400
  • 24/7 Emergency Service
  • Licensed & Insured
  • 5.0★ Rated on Google
  • Based in Lakeside, CA

10031 Maine Ave, Lakeside, CA 92040

Request a quote

Request your service

No obligation. We never sell your info.

Request Service

Tell us what's going on and our San Diego team will reach out. For emergencies, call us 24/7 at (619) 713-0400.

Loading form. If it does not load, please use the other contact options on this page.

By submitting, you agree to our Privacy Policy and Terms & Conditions. If you opt in to texts, message & data rates may apply and you can reply STOP to opt out.

Call Now Request Service