Cooling Tower Range
Range is the temperature drop across a cooling tower: hot condenser water in minus cooled water out. Range is set by the heat the chiller rejects and the water flow; a collapsing range usually points to a flow problem, not the tower itself.
Why It Matters
When a facility manager sees a tower 'not cooling', the fix depends on whether range or approach has moved — range problems often trace to pumps, strainers or valves, which changes who you call and what you budget.
What To Do About It
Log entering and leaving water temperatures with the chiller load. Range falling while the chiller works harder is a condenser-water-flow problem to chase at the pump and strainers.